Permit: T01EL01296

Parcel: 118051740


Addresses:

1702 S VIA ELNORA

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
07/26/2001 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
07/24/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0999*NO INSPECTION. MUST PAY REFEE BEFORE INSPECTION.
06/26/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0999*A REINSPECTION FEE IS DUE BEFORE THE NEXT INSPECTION 1.) CONDUIT FITTING IS STILL CROSS THREADED. 2.) JUMPER INSTALLED FROM SUB PANEL GROUND BAR TO FRAME IS A) UNDERSIZED FOR 60 AMP FEEDER B) TERMINATED UNDER DEDICATED SCREW USED TO ATTACH BOX. C) HAS A COUNTER CLOCKWISE WRAP UNDER SCREW. D) NEEDS A STA-KON' TYPE OF CRIMP FOR STRANDED CONDUCTOR 3.) NEUTRAL BAR AT SUB PANEL IS STILL NOT ISOLATED. REMOVE FACTORY JUMPER. 4.) GAS BOND GROUND WIRE CROOKED INSTALL STRAIGHT AND WILL NEED MORE STRAPS. 5.) GROUND WIRE IN ACORN CLAMP STILL NOT TERMINATED INWEDGE OF ACORN NOTE: PLEASE RETERMINATE EXISTING TELEPHONE GROUND.
06/07/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0210* A REFEE IS DUE BEFORE THE NEXT INSPECTION.EMT CONECTOR AT SUB PANEL IS
CROSS THREADED,PLEASE REDO.YOU INSTALLED AN ISOLATED GROUND BAR WHICH NEEDS TO HAVE A JUMPER TO THE SUB PANEL CAN (FRAME).YOU LEFT THE EXIST.NEUTRAL BAR W/GROUND WIRE STILL ATTACHED AND THE BONDING JUMPER INSTALLED!
NEED DEAD FRONT COVER.SCRAPE WATER BOND CONNECTION.NEED GAS BOND.DRIVE ROD FLUSH OR BELOW GRADE AND INSERT WIRE CORRECTLY INTO ACORN CLAMP WEDGE.REMOVE EXIST,GROUND ELECTRIC,FROM NEUTRAL AT SUB PANEL.
05/29/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0999*1)MORE SERVICE CONDUCTOR IN BOX AWAY FORM SCREW HOLE.2)NEED PERMANENT ADDRESS PER CITY AMENDMENT.3)EMPROPER USE OF EMT CONNECTOR TO TERMINATE INTO SEWER PANEL.4)EXSITING SERVICE AREA REQUIRED A 60 AMP.DERATE FOR 114 DEGREES-F AND INCREASE WIRE SIZE ACCORDINGLY (OVER ROOF AREA).5)NEED FULL COLOR CODEING FOR ON WIRE FOR NEUTRAL AND GROUNDWIRE.6)NEED GROUNDING ELECTRODE SYSTEM.