Inspection History Details
Inspection Status: Approved
Inspection History: SIGN ELECTRIC
Permit Number - T01EL01286
Inspection Description - SIGN ELECTRIC
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/07/2001 | SIGN ELECTRIC | Approved | IVRS - Inspection 0000* | |
06/04/2001 | SIGN ELECTRIC | Denied | IVRS - Inspection 0999*1)TRANSFORM BOX NOT BONDED TO GROUND.2)GROUNDING CONDUCTORS MISSING PROPER SPLICE CAP.3)FILL UNUSED OPENING AT J-BOX ON PRIMARY LINE.4)FLEX CONDUIT IN EXCESS OF 3 1/2'IN LENGTH NEEDS TO BE SECURED AT EACH END AND FOR EVERY 4' OF LENGTH.5)POT COVERS BACK ON EXPOSED J-BOXES.6)INSTALL DISCONNECT SWITCHES TO TRANSFORMERS.7)TIGHTEN ALL LOOSE FLEX CONDUIT FITTINGS.8)RESTORE FIRE-WALLS DAMAGED DURING SIGN INSTALLATION.9)SIGN TURED OFF AT BREAKER PANEL UNTIL IT PASSES INSPECTION. |