Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T01EL01285
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/09/2001 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000*OK TEMP SERVICE INSTALLATION POWER ALLREADY CLEARED. | |
07/25/2001 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999*1.) NEED HOLD DOWN DEVICES FOR BACK FED BREAKERS 384-16 2.) USE CORRECT SIZE WIRE OR ADAPTORS CAN NOT WHITTLE WIRE DOWN TO SIZE. 3.) NEED MAIN BREAKER AT EACH SERVICE 241-21 (5) 4.) NEED TO HAVE PLANS APPROVED BY CITY OK TO COVER TRENCH. | |
07/16/2001 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999*1.) NEED TO HAVE ALLWORK ENTER ON PERMIT. 2.) NEED TO VERIFY 2 GROUND ROD.3.) MISSING DEAD FRONT 3.) MISSING DEAD FRONT 4.) IDENTIFY SERVICES 5.) NEED HOLD DOWN DEVICE FOR BACK FEED BREADKER 384-16 6.) RISER TO PROTECT CONDUCTOR TO BELOW GRADE. 7.) NEED TO SEE ALL CONDUCTORS AND SPLICES 8.) STRAP GROUNDING ELECTRODE CONDUCTOR 9.) FILL UNUSED OPENING IN PANEL. 10.) LABEL BREAKERS 11.) DOUBLE LUGING AT GROUND BAR.12.) USE CORRECT STRAPS TO HOLD RISER 13.) MUST APPLY TAP RULES AS PER CODE 14.) NEED TO SEE MORE OF CONDUCTORS TO DETER SIZE AND RATING. 15.) NEED APPROVED PLANS TO VERIFY LOAD CACULATIONS. | |
07/12/2001 | ELECTRIC - FINAL | Partial Approval |