Permit: T01EL01276


Addresses:

3302 E GLENN ST

Inspection Status: Partial Approval

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
06/26/2001 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*
06/01/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0245*1)PERMIT OBTAINED IS FOR 60 AMP TO 100 AMP SERVICE UPGRADE.SERVICE EQUIP.
INSTALLED BY CONTRACTOR IS A 400 AMP, 5 METER PAE, FOR 5-UNITS.2)PLEASE PROVIDE LOAD CALC'S BY ELECTRICAL ENGINNEER. TO RAY MAJUTA OR FAX 791-3205 PRIOR TO RELEASE FOR POWER.3)INSTALL BOND BUSHINGS PER ART 250-94 N.E.C. BOTH ENDS OF EMT NIPPLES, J-BOX AND SERVICE ENCLOSURE.4)INSTALL PLASTIC BUSHINGS AT ALL FEEDER TERMINATIONS 300-4 N.E.C.5)INSTALL PERMANENT ADDRESS TAGS.6)NEED ACCESS TO INSPECT FEEDER TERMINATIONS.