Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - SERVICE UPGRADE
Permit Number - T01EL01263
Inspection Description - ELECTRIC - SERVICE UPGRADE
Inspection Status - Denied
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/27/2001 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection 0999*REFERED TO GENERAL INSPECTOR DOING ADDITION. | |
05/23/2001 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection 0999*1)CLEARANCE IN FRONT OF SERVICE NEEDS TO BE WIDTH OF SERVICE AND 3' IN FRONT OF ALL THE WAY TO THE FROUND.2)BURY GROUND WIRE AND DRIVE RODS TO BELOW GRADE.3)STRAP GROUND WIRE BY STORAGE SHED GOING UP WALL.OFFICE-ISSUE TO GENERAL INSPECTOR ADDITION ALSO GOING ON. |