Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO.
If you cannot find what you are looking for please
submit a records request.
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date |
Description |
Inspector |
Results |
Comments |
| 05/30/2001 |
ELECTRIC - SERVICE UPGRADE |
|
Approved |
IVRS - Inspection 0000* |
| 05/24/2001 |
ELECTRIC - SERVICE UPGRADE |
|
Denied |
IVRS - Inspection 0215* |
| 05/22/2001 |
ELECTRIC - SERVICE UPGRADE |
|
Denied |
IVRS - Inspection 0210*1)THE SERVICES ARE MOUNTED ABOVE THE 6'3" MAX HEIGHT PERMITTED. SEE TEP SERVICE MANUAL.2)THE WATER HEATERS INTERFER WITH THE CODE REQUIRED FREE AND CLEAR SPACE IN FRONT OF THE PANELS.SEE NEC ARTICLE 230,110,300,AND OTHER APPLICABLE SECTIONS.3)EACH SERVICE MUST HAVE ITS OWN GROUND WIRE UNLESS THE METERS ARE IN A COMMON ENCLOSURE (2 PAK METER CAN).4)THE GROUNDING MUST INCLUDE TWO GROUND RODS SET 6' FEET APART, THE GAS PIPE, AND THE WATER PIPE.5)TEP WILL PROBABLY REQUIRE METERS TO SET OUTSIDE OF STORAGE ROOMS. |