Permit: T01EL01262

Parcel: 129054220


Addresses:

2222 E EASTLAND ST

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
05/30/2001 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection 0000*
05/24/2001 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection 0215*
05/22/2001 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection 0210*1)THE SERVICES ARE MOUNTED ABOVE THE 6'3" MAX HEIGHT PERMITTED. SEE TEP SERVICE MANUAL.2)THE WATER HEATERS INTERFER WITH THE CODE REQUIRED FREE AND CLEAR SPACE IN FRONT OF THE PANELS.SEE NEC ARTICLE 230,110,300,AND OTHER APPLICABLE SECTIONS.3)EACH SERVICE MUST HAVE ITS OWN GROUND WIRE UNLESS THE METERS ARE IN A COMMON ENCLOSURE (2 PAK METER CAN).4)THE GROUNDING MUST INCLUDE TWO GROUND RODS SET 6' FEET APART, THE GAS PIPE, AND THE WATER PIPE.5)TEP WILL PROBABLY REQUIRE METERS TO SET OUTSIDE OF STORAGE ROOMS.