Permit: T01EL01236

Parcel: 123171830


Addresses:

1324 N VINE AV

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
06/01/2001 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection 0000*
05/29/2001 ELECTRIC - SERVICE UPGRADE Partial Approval IVRS - Inspection 0000*1)STRAP AND/OR BURY GROUNDING ELECTRODE CONDUCTOR AND BOND CONDUCTOR.2)DOUBLE LUGING OF BREAKER.3)FINISH INSTALLING BREAKERS-LOOSE CONDUCTORS IN PANEL TO BE TERMINATED.
05/20/2001 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection 0999*1)BOND AROUND CONCRETE KNOCKOUT.2)LOOSE FITTING AT JUNCTION BOX AND CONDUIT RUNS.3)LA BBL BREAKERS.4)NEED GAS BOND.5)DRIVE GROUND R0DS FLUSH OR BELOW GRADE.6)CLEAN UP ALL UNSAFE WIRING CONDITONS IN LAUNDRY SHED.7)SUPPORT CONDUIT BELOW PANEL AS PER CODE.8)PROTECT NM CABLE WHERE ENTERS CONDUIT SLEEVE.