Inspection History: ELECTRIC - FINAL
Permit Number - T01EL01228
Inspection Description - ELECTRIC - FINAL
Inspection Status - Denied
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/17/2001 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999*DENIED,1)SHOPLIGHTS TO BE PROPERLY WIRED-NOT EXTENTION CORD OR OPEN SPLICES.2)TERMANATE OR REMOVE OLD ROMEX CABLES.3)USE OF EXTENTION CORDS TO PAINT BOOTH NOT ALLOWED.4)HOME MADE EXTENTION CORDS NOT ALLOWED-USE APPROVED AND LISTED CORDS.5)MISSING BACK PLATE.6)IMPROPERLY WIRED COMPRESSORS-USE OF ROMBX NOT ALLOWED.7)SECURE TIME CLOCK IN BATHROOM AND USE APPROVED JUNCTION BOX COUIER.8)IMPROPERLY INSTALLED MIXING STATION -INSTALL ASPER CODE.9)PAINT MIXING ROOM NOT UP TO CODE-ELECTRIC PANELS AND DISCONECTS INSTALLED IN ROOM.10)HAVE LICENSED L-11 ELECTRICAL CONTRACTOR BRING BUILDING UP TO CODE INSIDE AND OUTSIDE AND OUTSIDE*PLEASE REFERENCE ARTICLES 511 AND 516.11)SERVICE IN DELAPIDATED AND UNSAFE CONDITION.12)NEED GENERAL REPAIR PERMIT FOR BUILDING INSPECTOR TO ACCESS STRUCTUAL INTEGRITY.13)NEED C OF O FIRE APPROVAL INSPECTION. |