Permit: T01EL01227

Parcel: 13824093D


Addresses:

1641 W COMMERCE CT

Inspection Status: Approved

Inspection History: ELECTRIC - RECONNECT

Date Description Inspector Results Comments
06/19/2001 ELECTRIC - RECONNECT Approved IVRS - Inspection 0000*
06/14/2001 ELECTRIC - RECONNECT Denied IVRS - Inspection 0920*LOCKED NO ACCESS.CALLED NUMBER LEFT ON IVR AND NO ANSWER.PLEASE HAVE UNIT OPEN FOR INSPECTION.
05/24/2001 ELECTRIC - RECONNECT Denied IVRS - Inspection 0245*1)OUTSIDE RECEPTACLE IN BACK METER NEEDS TO BE GFCR PROTECTED AND WEATHER PROOF COVER INSTALLED.2)RE-SUPPORT CONDUIT RUN ALONG INSIDE SOUTH WALL BY PANEL BOARDS, AND BOXES.3)SECURE WIRING AND INSTALL COVERS ON J-BOXES, LB'S, THRU-OUT BLD, INTERIOR.4)REPAIR BROKEN EM. BATTERU LIGHTS ABOVE COLUMNS CENTER AREA.5)INSTALL BLANKS
IN UNUSED BREAKER SLOTS IN PANEL NORTH END OF BUILDING.6)COMPLETE REPAIRS AND RE-CALL INSPECTION.REPAIR TO BE MADE BY L-11 LICENSED ELECTRICAL CONTRACTOR.
05/18/2001 ELECTRIC - RECONNECT Denied IVRS - Inspection 0920*LOCKED MUST BE OPEN.
PLEASE RECALL INSPECTION.