Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - RECONNECT
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/19/2001 | ELECTRIC - RECONNECT | Approved | IVRS - Inspection 0000* | |
| 06/14/2001 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection 0920*LOCKED NO ACCESS.CALLED NUMBER LEFT ON IVR AND NO ANSWER.PLEASE HAVE UNIT OPEN FOR INSPECTION. | |
| 05/24/2001 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection 0245*1)OUTSIDE RECEPTACLE IN BACK METER NEEDS TO BE GFCR PROTECTED AND WEATHER PROOF COVER INSTALLED.2)RE-SUPPORT CONDUIT RUN ALONG INSIDE SOUTH WALL BY PANEL BOARDS, AND BOXES.3)SECURE WIRING AND INSTALL COVERS ON J-BOXES, LB'S, THRU-OUT BLD, INTERIOR.4)REPAIR BROKEN EM. BATTERU LIGHTS ABOVE COLUMNS CENTER AREA.5)INSTALL BLANKS IN UNUSED BREAKER SLOTS IN PANEL NORTH END OF BUILDING.6)COMPLETE REPAIRS AND RE-CALL INSPECTION.REPAIR TO BE MADE BY L-11 LICENSED ELECTRICAL CONTRACTOR. |
|
| 05/18/2001 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection 0920*LOCKED MUST BE OPEN. PLEASE RECALL INSPECTION. |