Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 06/01/2001 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 05/17/2001 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*DENIED,1)PANEL BUSS IS DAMAGED 2-SPACES RENDERED UN USEABLE-NEED TO REPLACE BUSS.2)LOOSE FITTING AT L.B.3)TIGHTEN TO SEAL MEYERS HUB.4)CONDUIT SYSTEM CAN NOT BEUSED AS GROUND PATH FOR PHONE.5)CAN NOT RUN ROMEX IN CONCREAT OF WALL USE LISTED AND APPROVED CABLE. |