Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO.
If you cannot find what you are looking for please
submit a records request.
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 05/22/2001 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 05/17/2001 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*1)CEILING IN SOUTH WEST BEDROOM NOT PROPERLY INSTALLED/HAZARDOUS WIRING.2)ALL SWITCH AND PLU RECEPTACLE COVER PLATES MUST BE INSTALLED.3)CEILING IN SOUTH WEST BEDROOM NOT PROPERLY INSTALLED/HAZARDOUS WIRING. |