Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T01EL01198
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/20/2001 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* | |
07/13/2001 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999*1.) SEAL 2" OPENING AT OLD SERVICE 860 E 16TH WHICH USE TO FEED SUITE WHERE NEW SERVICE INSTALLED. 2.) JUNCTION BOX TO HAVE CONDUCTORS TAPED WITH CORRECT PHASE, AND NEUTRAL COLORS. 3.) 200 AMP DISCONNECTS TO BE LABELED A AND B 4.) LABEL NEW PANEL "B" AND INSTALL CIRCUIT BREAKER COVER ON OPEN SLOT. 5.) PANEL B NOT TO BE BLOCKED. | |
06/08/2001 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*1. OK TO CLEAR SERVICE INCREASE FOR CHANGE OVER. 2. PROVIDE REJECT PINS AT EACH FUSE IN 200 AMP DISCONNECTS. 3. PROVIDE PROTECTION FOR GROUND RODS, WEST ONE WORST, TRIP HAZZARD. CALL FOR FINAL ONCE CHANGE OVER COMPLETE. |