Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
Permit Number - T01EL01171
Inspection Description - ELECTRIC - SERVICE UPGRADE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/30/2001 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection 0000* | |
| 05/24/2001 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection 0215*1)EACH UNIT MUST HAVE ITS OWN J. BOX, TO PREVENT ACCESS TO ITS FEEDER CONDUCTORS.2)THE GROUNDING IS INCORRECT-SEE SAMPLE DIAGRAM.3)I DENTIFY EACH SERVICE WITH ADDRESS LABL.USE EMBOSSED METAL (DYMO) TAPE-SCREW OR RIVET TO PANELS.DO NOT USE "MAGIC MARKER".4)CALL TEP-ASK FOR YOUR AREA REP. AND REQUEST INSPECTION OF SERVICE ENTRANCE.I BELIEVE EMT IS NOT ALLOWED FOR RISER PIPE. | |
| 05/22/2001 | ELECTRIC - SERVICE UPGRADE | Not ready for Inspection | IVRS - Inspection 0000*1)RISER HIGHT TO ACCOMADATE 12' CABLE DROP CLEARANCE OVER DRIVEWAY.2)TENANT ON WEST UNIT MUST HAVE ACCESS TO SERVICE.(FENCE BETWEEN UNITS).3)COMPLETE SERVICE.4)DUPLEX WITH 2 SERVICES REQUIRES LICENSED CONTRACTOR. LEAVE NAME AND PHONE #. |