Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T01EL01171

Parcel: 129054220


Addresses:

2220 E EASTLAND ST


Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Permit Number - T01EL01171

Inspection Description - ELECTRIC - SERVICE UPGRADE

Inspection Status - Approved

Date Description Inspector Results Comments
05/30/2001 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection 0000*
05/24/2001 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection 0215*1)EACH UNIT MUST HAVE ITS OWN J. BOX, TO PREVENT ACCESS TO ITS FEEDER CONDUCTORS.2)THE GROUNDING IS INCORRECT-SEE SAMPLE DIAGRAM.3)I DENTIFY EACH SERVICE WITH ADDRESS LABL.USE EMBOSSED METAL (DYMO) TAPE-SCREW OR RIVET TO PANELS.DO NOT USE "MAGIC MARKER".4)CALL TEP-ASK FOR YOUR AREA REP. AND REQUEST INSPECTION OF SERVICE ENTRANCE.I BELIEVE EMT IS NOT ALLOWED FOR RISER PIPE.
05/22/2001 ELECTRIC - SERVICE UPGRADE Not ready for Inspection IVRS - Inspection 0000*1)RISER HIGHT TO ACCOMADATE 12' CABLE DROP CLEARANCE OVER DRIVEWAY.2)TENANT ON WEST UNIT MUST HAVE ACCESS TO SERVICE.(FENCE BETWEEN UNITS).3)COMPLETE SERVICE.4)DUPLEX WITH 2 SERVICES REQUIRES LICENSED CONTRACTOR. LEAVE NAME AND PHONE #.