Permit: T01EL01142

Parcel: 116240890


Addresses:

220 S CLAUSEN CI

Inspection Status: Partial Approval

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
05/24/2001 ELECTRIC - SERVICE UPGRADE Partial Approval IVRS - Inspection 0000*1)TEP LINE TO BE COVERED IN CONCRETE.2)ONCE SERVICE ENERGIZED- REMOVE
PARTIALLY DRIVEN GROUND ROD IN FRONT OF SERIVICE-WILL NOT BE REQUIRED.3)STRAP #4 COPPER WIRES TO WALL CALL ME BACK ONCE CHANGE OVER IS COMPLETED FOR A FINAL INSPECTION.
05/23/2001 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection 0999*1)GROUND RODS MUST COMPLY W/MIN REQUIREMENTS OF THE CODE.(APPEAL IS NOT AN EXCEPTION,BUT AN APPROVED METHOD.2)PAY REFEE.3)NEED THE NAME OF THE LICENCED L-11 OR C-11 ELECTRICAL CONTRACTOR FOR VERTICATION WITH ELECT.
05/15/2001 ELECTRIC - SERVICE UPGRADE Denied 1) GROUND ROD TO BE 2 1/2' DEEP 2) USE THE PROPER FITTING TO TERMINATE THE L.B. FITTING INTO BOX. 3) INSTALL WATER BOND ON INTERIOR SOILD COPPER THAT GOES INSIDE. A RE INSP FEE IS DUE
05/10/2001 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection 0999* 1) GROUND RODS MUST COMPLY WITH CODE. DRIVEN 2 1/2' DEEP ETC. 10" + OR HORIZONTAL NOT ACCEPTABLE
2) USE THE PROPER FITTING AT THE 1 1/2 C.B. ON EMT CONNECTOR NOT APPROVED 3) INSTALL INTERIOR WATER BOND ON SOLID COPPER LINE THAT GOES INSIDE