Inspection Status: Approved
Inspection History: SIGN ELECTRIC
| Date |
Description |
Inspector |
Results |
Comments |
| 07/06/2001 |
SIGN ELECTRIC |
|
Approved |
IVRS - Inspection 0000* |
| 07/02/2001 |
SIGN ELECTRIC |
|
Denied |
IVRS - Inspection 0999*1.) TIGHTEN LOCKNUTS FROM CONDUIT TO U BOXES INSIDE SIGNS TO PROVIDE PROPER BONDING 2.) LIFT CONDUIT OFF ROOF USING REDWOOD BLOCKING OR METAL UNISTRUTS. 3.) YOU MAY NOT DRIVE SCREWS DIRECTLY INTO ROOFING WITHOUT SEALING PUNCTURE AFTERWARDS. 4.) SIGN TO REMAIN OFF UNTIL ELECTRICAL INSPECTOR APPROVED |