Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/17/2001 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* | |
| 05/16/2001 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000* | |
| 05/14/2001 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0245* 1) NEW SUB PANELS AND CIRCUIT BREAKERS MUST BE ID'ED PANELS TO HAVE LABELS WITH UNIT OR SPACE MARKING. ART. 230-70 NEC #9287 CITY ORDIN. 2) GROUNDING ELECTRODE SYSTEM REQUIRED FOR SEPERATE BLDG'S ART. 250-32 NEC 3) SPILT BOLTS NOT ALLOWED FOR SPLICING GROUNDIND ELECTRODE CONDUCTOR ART 250-50 NEC 4) GAS PIPING SYSTEM MUST BE BONDED 250-104 5) BOND BUSHINGS REQUIRED AT MAIN SERVICE BOTH ENDS OF NIPPLES 250-94 NEC 6) ID CIRCUIT BREAKERS 7) IF THE RENTAL UNITS HAVE A GROUNDING ELECTRODE SYSTEM PLEASE EXPOSE FOR INSP. |