Permit: T01EL01128

Parcel: 111051610


Addresses:

3026 N SPARKMAN BL

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
05/17/2001 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
05/16/2001 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*
05/14/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0245* 1) NEW SUB PANELS AND CIRCUIT BREAKERS MUST BE ID'ED PANELS TO HAVE LABELS WITH UNIT OR SPACE MARKING. ART. 230-70 NEC #9287 CITY ORDIN. 2) GROUNDING ELECTRODE SYSTEM REQUIRED FOR SEPERATE BLDG'S ART. 250-32 NEC 3) SPILT BOLTS NOT ALLOWED FOR SPLICING GROUNDIND ELECTRODE CONDUCTOR ART 250-50 NEC 4) GAS PIPING SYSTEM MUST BE BONDED 250-104 5) BOND BUSHINGS REQUIRED AT MAIN SERVICE BOTH ENDS OF NIPPLES 250-94 NEC
6) ID CIRCUIT BREAKERS 7) IF THE RENTAL UNITS HAVE A GROUNDING ELECTRODE SYSTEM PLEASE EXPOSE FOR INSP.