Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/23/2001 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* | |
| 05/18/2001 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999*1)UNAPPROVED 50 A PLU RECEPTACLE OUTLET (MUST BE WEATHER PROOF) THE ONE YOU HAVE USED IS ONLY WEATHER PROOF WHEN CLOSED.INSPECTION STOPPED CONTRACTOR TO BE CONTACTED T.E.P. WILL BE ORDERED TO DISCONNECT POWER AT METER IF NECESSARY. | |
| 05/10/2001 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999* 1) NEC 225-19 NEED 3' CLEARANCE TO OVERHEAD CONDUCTORS IN ALL DIRECTIONS FROM EDGE OF ROOF AT TRAILER 2) NEC 550-5 A) POWER SUPPLY TO MOBILE HOME NOT TO EXCEED 50AMP B) POWER CORD TO MH TO HAVE FREE END TERMINATING IN ATTACHMENT PLUG CAP G) WHERE CORD TO MH PASSES THROUGH WALL (SKIRTING) IT SHALL BE PROTECTED BY CONDUIT 3) AT HOUSE SUB PANEL: 1) IMPROPER USE OF FITTINGS 2) DOUBLE AND TRIPLE LUGGED GROUNDED CONDUCTORS 3) IMPROPER GROUNDING ELECTRODE SYSTEM AT HOUSE 4) NEUTRAL AND GROUNDING CONDUCTORS TERMINATED ON SAME BUSBAR ETC... |