Permit: T01EL01107

Parcel: 125073240


Addresses:

432 N OLSEN AV

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
05/23/2001 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
05/21/2001 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*1)GAS BAND ON WRONG SIDE OF GAS METER.2)EXPOSE GROUNDING ELECTRODE SYSTEM.A RE INSPECTION FEE IS DUE BEFORE THE
NEXT INSPECTION.
05/15/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0245* 1)INSTALL GROUNDING ELECTRODE SYSTEM.2)INSTALL GAS BOND.3)INSTALL PERMANENT ADDRESS LABEL,SCREWED OR RIVITED TO ENCLOSURE.4)INSTALL SEALING LOCKNUTS WITH BOND BUSHING ON PENITRATIONS ABOVE BREAKER AREA.5)USE 1/4" BOLTS OR SCREWS TO SUPPORT SERVICE ENCLOSURE AND RISER CONDUIT # 10 PLASTIC ANCHORS NOT APPROVED.6)INSTALL BRACE FOR 10' RISER.