Inspection Status: Denied
Inspection History: ELECTRIC - UNDERGROUND
| Date |
Description |
Inspector |
Results |
Comments |
| 07/23/2001 |
ELECTRIC - UNDERGROUND |
|
Denied |
PLEASE CONSULT WITH YOUR TUCSON ELECTRIC POWER CO. DISTRICT REP. REGARDING THE DEPTH, LOCATION, AND ROATING OF THE TRENCH.THEY HAVE JURISDICTION OVER THE INCOMING ELECTRIC SERVICE CABLES. APPROVAL OF THESE INSPECTION DOES NOT GUARANTEE TEP WILL INSTALL THE POWER CABLES. |
| 07/16/2001 |
ELECTRIC - UNDERGROUND |
|
Denied |
IVRS - Inspection 0245*1.) NO COMPLIANCE WITH ITEM #1 & 5. 2.) LOCK NUTS LOOSE ON RISER, RISER CONDUIT LOOSE, DRYWALL SCREW NOT STRONG ENOUGH FOR SUPPORT. USE MIN. 1/4 BOLTS FOR RISER SUPPORT 3.) NEED ACCESS INTO UNIT TO INSPECT BRANCH CIRCUIT ROUTING AND CONNECTIONS 4.) NEED TO VERIFY GAS BOND. |
| 07/12/2001 |
ELECTRIC - UNDERGROUND |
|
Denied |
IVRS - Inspection 0245*1.) INSTALL BOND BUSHINGS ON RISER CONDUITS 250-94 NEC. 2.) GAS BOND TO BE ON CUSTOMER SIDE OF METERS. 3.) NO COMPLIANCE WITH ITEM #1. 4.) NO COMPLIANCE WITH ITEM #5 RENTAL ON PROPERTY ALSO BEING UPGRADED. |
| 07/06/2001 |
ELECTRIC - UNDERGROUND |
|
Denied |
IVRS - Inspection 0245*1.) SPLICES NOT ALLOWED FOR GROUNDING ELECTRODE CONDUCTOR UNLESS BY EXOTAERMIC OR IRREVERSIBLE CRIMP. 250-50 N.E.C. 2.) GAS & WATER PIPING MUST BE BONDED 250-104 N.E.C. 3.) PERMANENT ADDRESS LABELS ON METERS ENCLOSURES 230-70 N.E.C. #9287 CITY ORDIN. 4.) ADDRESS ON METERS MUST REFLECT ADRESS ON PERMIT /PERMITS. 5.) FOR OCCUPANCYS OR APTS, FOR RENT ELECTRICAL WORK MUST BE DONE BY LICENSED ELECTRICAL CONTR. PLEASE LEAVE NAME AND PH# OF CONTR. FOR VERIFICATION. |