Permit: T01EL01056

Parcel: 125080020


Addresses:

2222 E 8TH ST

Inspection Status: Partial Approval

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
05/08/2001 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000* 1) OK TO CLEAR TEMP POWER
2) OK CABLE DROP
05/03/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0245* 1) INSTALL RISER CONDUIT
2) BOND GAS PIPE. 250-104 NEC 3) 2" HUB AT TOP OF PANEL INSTALLED TO FAR IN FRONT AREA BEYOND THE PANEL DEAD FRONT. THIS DOES NOT ALLOW THE DEAD FRONT TO PROPERLY SEAT IN MANUFACTURER'S DESIGNATED SLOTS WITH OUT BINDING. MOVE HUB BACK AND PROPERLY SEAL TOP PENETRATION. ART 110-3 A,B 4) GROUND LUG IN J BOX NOT INSULATED PROPERLY, SHEET METAL SCREW NOT ALLOWED, MUST LAY ON FLAT SURFACE (CHECK LISTING FOR INSTALLATION), ENAMEL MUST BE SCRAPED OFF TO ENSURE ELEC. CONTINUITY. ART. 250-12, 250-96, 250-8, NEC 5) SPLICES IN 12X12 J BOX NOT ADEQUETLY WRAPPED WITH TAPE, TAPE IS BEGINING TO UNWRAP AND IS SPRING LOADED AGAINST COVER. WRAP SPLICES TO ENSURE INTEGRITY OF INSULATING FACTORS, AND BRACE OR REFORM WIRING SPLICE JOINTS AWAY FROM COVER ART. 110-14 B NEC 6) PHASE TAPE CONDUCTORS # 6 OR LARGER TO INDICATE UNGROUNDED, GROUND CONDUCTORS, 200-6, 210-4 NEC