Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T01EL01010

Parcel: 11103053A

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T01EL01010

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
05/10/2001 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
05/07/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0999* 1) UNCOVER 2ND GROUND ROD AT NEW PEDISTAL 2) BOND GROUNDING ELECTRODE CONDUCTOR TO NEUTRAL AND TO GROUNDING LUG AT NEW PEDISTAL 3) INSTALL NEW GROUND RODS FOR PEDISTAL #48 4) BOND NEW MADE GROUNDING ELECTRODE TO NEUTRAL AND TO PEDISTAL EQUIPMENT GROUNDING LUG