Permit: T01EL01000

Parcel: 123112490

Inspection Status: Partial Approval

Inspection History: ELECTRIC - CABLE DROP

Permit Number - T01EL01000

Inspection Description - ELECTRIC - CABLE DROP

Inspection Status - Partial Approval

Date Description Inspector Results Comments
05/27/2001 ELECTRIC - CABLE DROP Partial Approval IVRS - Inspection 0000*
05/25/2001 ELECTRIC - CABLE DROP Partial Approval 1)CURRENTLY IDENTIFY CONDUCTORS-YOU HAVE A NEUTRAL CONDUCTOR GOING TO THE BREAKER.OK CABLE DROP.
05/14/2001 ELECTRIC - CABLE DROP Denied IVRS - Inspection 0999* 1) GROUND RODS TO BE 6' APART 2) FILL ALL UNUSED OPENINGS 3) NEED TO USE SEALING FITTINGS ABOVE AND ON SIDE OF BUSS 4) CORRECTLY ID CONDUCTORS 5) SEAL TITE CONDUIT OVER FILLED FOR CONDUCTOR SIZE
6) STRAP SEAL TITE CONDUIT AS PER CODE 7) LABEL ALL BREAKERS 8) NEED PERMANENT METAL ADDRESS LABEL 9) USE BREAKERS APPROVED FOR USE BY MANUFACTURER. NOTE: UNSAFE CONDUITS ARE NOT GRAND FATHERED AS EXSISTING