Inspection History Details
Inspection Status: Partial Approval
Inspection History: ELECTRIC - CABLE DROP
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/27/2001 | ELECTRIC - CABLE DROP | Partial Approval | IVRS - Inspection 0000* | |
| 05/25/2001 | ELECTRIC - CABLE DROP | Partial Approval | 1)CURRENTLY IDENTIFY CONDUCTORS-YOU HAVE A NEUTRAL CONDUCTOR GOING TO THE BREAKER.OK CABLE DROP. | |
| 05/14/2001 | ELECTRIC - CABLE DROP | Denied | IVRS - Inspection 0999* 1) GROUND RODS TO BE 6' APART 2) FILL ALL UNUSED OPENINGS 3) NEED TO USE SEALING FITTINGS ABOVE AND ON SIDE OF BUSS 4) CORRECTLY ID CONDUCTORS 5) SEAL TITE CONDUIT OVER FILLED FOR CONDUCTOR SIZE 6) STRAP SEAL TITE CONDUIT AS PER CODE 7) LABEL ALL BREAKERS 8) NEED PERMANENT METAL ADDRESS LABEL 9) USE BREAKERS APPROVED FOR USE BY MANUFACTURER. NOTE: UNSAFE CONDUITS ARE NOT GRAND FATHERED AS EXSISTING |