Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/23/2001 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection 0000* | |
| 05/01/2001 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection 0000* NEED TO SEE AFTER CROSS OVER | |
| 04/26/2001 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection 0210* 1) THE COLD WATER PIPING AND THE GAS PIPING MUST ALSO BE BONDED TO THE NEW PANEL SEE NEC ART. 250-152 2) "MAGIC MARKER" IS NOT ACCEPTABLE AS A PERMANENT MEANS OF IDENTIFYING THE SERVICE . USE METAL STICK ON #'S OR ALUMINUM DYMO TAPE WITH SCREWS PLEASE CORRECT AND RECALL |