Inspection History Details
Inspection Status: Partial Approval
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/14/2001 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000* NEED TO SEE AFTER CROSS OVER | |
| 05/10/2001 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999* 1) VERIFY GAS BOND 2) NEED PERMANENT METAL ADDRESS LABEL 3) LABEL BREAKERS 4) NEED ALL SCREWS IN HUB FOR RISER 5) NEED TO SEE METHODS FOR REFEEDING OF CIRCUITS 6) WILL NEED TO SEE AFTER CROSS OVER 7) PLEASE STRAP GROUNDING ELECTRODE CONDUCTOR |