Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/05/2001 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* | |
| 05/31/2001 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0245*1)IMPROPER USE OF CONNECTER ON LB, USE CLOSE NIPPLE WITH LOCKNUTS BOTH ENDS AND BOND BUSHING ART 250-94 NEC.2)INSTALL BREAKER BLANKS ON DEAD FRONT OF PANEL.3)GROUND ROD EXPOSED 3" ABOVE GROUND IS TRIP HAZARD, POUND DOWN FLUSH WITH EARTH. | |
| 04/24/2001 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0245* 1) 1" IMC DOWN WALL NOT SUPPORTED PROPERLY, USE APPROPIATE BACKING SUPPORT ON CONDUIT, OR BEND OFFSET SO CONDUIT IS AGAINST WALL 2) PHASES NEUTRAL SUB PANEL FEEDER WHITE, 3) INSTALL PERMANENT ADDRESS LABEL, RIVIT OR SCREW TO ENCLOSURE 4) ID CIRCUIT BREAKERS CALL FOR FINAL WHEN COMPLETE. CALLED AND LEFT MESSAGE WITH JULIE(TEP ) AS CUSTOMER REQUESTED |