Permit: T01EL00950

Parcel: 104060170


Addresses:

4001 N ROMERO RD

Inspection Status: Approved

Inspection History: ELECTRIC - RECONNECT

Date Description Inspector Results Comments
07/22/2001 ELECTRIC - RECONNECT Approved IVRS - Inspection 0000*IJ TI RECONNECT WILL ADD ELECTRIC FOR ROOF UNITS TO NEW PERMITS FOR A/C & COOLERS.
07/18/2001 ELECTRIC - RECONNECT Denied IVRS - Inspection 0999*
05/23/2001 ELECTRIC - RECONNECT Denied IVRS - Inspection 0999*1)POOL AREA-UN-COPPED LIGHT BOX.2)PANEL BACK ROOM-BLANKS NEEDED.3)ROOF AREA BADLY DAMAGED WIRING TO COOLERS AND AC'S.4)SERVICE NEEDS 2 GROUND RODS,REMOVE ALL DOUBLE LUGGING.5)VERY MINOR CLEAN UP DONE-WENT OVER PROBLEMS WITH BUCK (SAGUARO ELECT) TO GO OVER PROBLEMS AND WHAT NEEDS TO BE REPAIRED.
04/27/2001 ELECTRIC - RECONNECT Denied IVRS - Inspection 0999* 1) REAR OUTSIDE REPAIR BROKEN CONDUIT WITH WIRING 2) LIGHT ABOVE REAR DOOR MISSING 3) SERVICE DISCONNECT (200AMP) TO BE CLEANED UP VARIOUS DOUBLE LUGGING (NOT ALLOWED) 4) SERVICE IS NOT GROUNDED ONLY WATER BOND INSTALL 2 GROUND RODS 6' APART WITH #4 6) LABEL SERVICE WITH ADDRESS (PERMANENT) 7) DISCONNECT FOR COMPRESSOR OUTSIDE (SOUTH) HAS TO CLOSE
8) AT FRONT ENTRY INSTALL WIRING IN CONDUIT
9) INSIDE BAR AREA ALL WIRING TO BE CLEANED UP EXPOSED ROMEX TO BE IN CONDUIT MISSING LIGHTS TO BE PROPERLYCAPPED OFF YOU NEED TO HAVE A L-11 ELEC. CONTRACTOR DO ELEC. CLEN UP ON THIS PLACE THEN RECALL FOR INSP.
04/26/2001 ELECTRIC - RECONNECT Denied IVRS - Inspection 0999* YOUR MESSAGE DIDN'T GET RECORDED ON IVR PLEASE CALL EXT 126 JUDY AND RESCHEDULE