Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/05/2001 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* | |
| 04/26/2001 | ELECTRIC - FINAL | Not ready for Inspection | 1) CHASE NIPPLE NOT APPROVED(3/4"LB) USE CLOSE NIPPLE, LOCKNUT ON BOTH ENDS 250-94 NEC 2) SPILT BOLT TAPING NOT ADEQUATE IN J BOX FOR SUB PANEL, TOO THIN, USE RUBBER TAPE FIRST THEN VINAL. MUST EQUAL THE INSULATION OF CONDUCTOR BEING SPLICED. 3) DRYWALL OR DECK SCREWS NOT ACCEPTABLE FOR SUPPORT OF RISER CONDUIT, USE 1/4" LAGS MIN. 4) WATER SOFTNER IN VIOLATION OF WORKING SPACE FOR SERVICE 110-26 NEC 5) GROUND J BOXES 370-4, 250 NEC |