Permit: T01EL00926

Parcel: 127070660


Addresses:

5101 E 9TH ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
10/05/2001 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
04/26/2001 ELECTRIC - FINAL Not ready for Inspection 1) CHASE NIPPLE NOT APPROVED(3/4"LB) USE CLOSE NIPPLE, LOCKNUT ON BOTH ENDS 250-94 NEC
2) SPILT BOLT TAPING NOT ADEQUATE IN J BOX FOR SUB PANEL, TOO THIN, USE RUBBER TAPE FIRST THEN VINAL. MUST EQUAL THE INSULATION OF CONDUCTOR BEING SPLICED. 3) DRYWALL OR DECK SCREWS NOT ACCEPTABLE FOR SUPPORT OF RISER CONDUIT, USE 1/4" LAGS MIN. 4) WATER SOFTNER IN VIOLATION OF WORKING SPACE FOR SERVICE 110-26 NEC 5) GROUND J BOXES 370-4, 250 NEC