Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date |
Description |
Inspector |
Results |
Comments |
| 04/17/2001 |
ELECTRIC - SERVICE UPGRADE |
|
Approved |
IVRS - Inspection 0000* OK TO CLEAR SERVICE UPGRADE |
| 04/13/2001 |
ELECTRIC - SERVICE UPGRADE |
|
Denied |
IVRS - Inspection 0999*1. INSTALL LISTED 200 A MAIN CIRCUIT BREAKER 2. INSTALL MURRY CIRCUIT BREAKER 60 AMO OR 50A 3. NEED 2 SUPPORTS ON RISER, ONE BELOW & ONE ABOVE 4. NEED ROOF JACK 5. ID NEUTRAL ABOVE ROOF 8-10" OUT OF WWEATHER HD. 6. INSTALL GROUNDING SYSTEM, 2 GROUND RODS 6' APART WITH # 4 COPPER TO SERVICE 8.BOND GAS & WATER LINE 9. INSTALL INSERT PLASTIC BUSHING WHERE # 6'S COME OUT OF WALL. |