Permit: T01EL00854

Parcel: 134110020


Addresses:

7911 E ELI PL

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
04/17/2001 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection 0000*
04/13/2001 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection 0245*NOTES: 1. CHASE NIPPLE WITH GROULD WIRE WRAPPED AROUND IT NOT AN APPROVED WIRING METHOD, USE CLOSE NIPPLE WITH LOCKNUTS BOTH ENDS.A AEALING COCKNUT INSIDE ENCLOSURE WITH BOND BUSHING. 2. INSTALL SLEVE WHERE BRANCH CIRCUITS ENTER HOUSE, USE APPROVED CONNECTOR & SEAL PROPERLY.3. USE MINIMUM 1/4 ANCHORS OR BOLTS FOR RISER SUPPORT NOT # 10 SCREWS, & RE-INSTALL 2-HOLE STRAP CORRECTLY. 4.PERMANENT ADDRESS LABEL REQUIRED, SCREWED OR RIVITED, NO MARKING PEN.