Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date |
Description |
Inspector |
Results |
Comments |
| 04/17/2001 |
ELECTRIC - SERVICE UPGRADE |
|
Approved |
IVRS - Inspection 0000* |
| 04/13/2001 |
ELECTRIC - SERVICE UPGRADE |
|
Denied |
IVRS - Inspection 0245*NOTES: 1. CHASE NIPPLE WITH GROULD WIRE WRAPPED AROUND IT NOT AN APPROVED WIRING METHOD, USE CLOSE NIPPLE WITH LOCKNUTS BOTH ENDS.A AEALING COCKNUT INSIDE ENCLOSURE WITH BOND BUSHING. 2. INSTALL SLEVE WHERE BRANCH CIRCUITS ENTER HOUSE, USE APPROVED CONNECTOR & SEAL PROPERLY.3. USE MINIMUM 1/4 ANCHORS OR BOLTS FOR RISER SUPPORT NOT # 10 SCREWS, & RE-INSTALL 2-HOLE STRAP CORRECTLY. 4.PERMANENT ADDRESS LABEL REQUIRED, SCREWED OR RIVITED, NO MARKING PEN. |