Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/17/2001 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000*PYRAMID ELECT CONTRACTOR -CONTRACTOR OF RECORD. | |
| 05/03/2001 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999* 1) THE 2" RIGID RISER ON #1 SERVICE HAS TO HAVE 2 SUPPORTS AND SHEET METAL SCREWS TOO LIGHT USE AT LEAST 1/4" 2) THE 2" PVC ABOVE GROUND IS REQUIRED TO BE SCHEDULE 80, SCHEDULE 40 ONLY ALLOWED BURRIED 3) 99NEC SECTION 370-28 A-2 WHERE ANGLE OR 4 PULLS MADE THE JUNCTION BOX IS FIGURED BY MULTIPLYING THE CURGEST CONDUIT ENTRY (2"PVC) TIMES 6=12". A JUNCTION BOX 12"X12" IS THE MINIMUM REQUIRED. THE 6X6X4 IS TOO SMALL 4) UNDER STAND THE GAS BOND TO BE INSTALLED WHEN GAS LINE IS FINISHED |
|
| 04/23/2001 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999* | |
| 04/20/2001 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999* IN ORDER TO BE ABLE TO DO THIS KIND OF WORK YOU MUST HAVE A C-11 ELECTRICAL LICENCED CONTRACTOR |