Permit: T01EL00837

Parcel: 120074090

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
05/17/2001 ELECTRIC - FINAL Approved IVRS - Inspection 0000*PYRAMID ELECT CONTRACTOR -CONTRACTOR OF RECORD.
05/03/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0999* 1) THE 2" RIGID RISER ON #1 SERVICE HAS TO HAVE 2 SUPPORTS AND SHEET METAL SCREWS TOO LIGHT USE AT LEAST 1/4"
2) THE 2" PVC ABOVE GROUND IS REQUIRED TO BE SCHEDULE 80, SCHEDULE 40 ONLY ALLOWED BURRIED 3) 99NEC SECTION 370-28 A-2 WHERE ANGLE OR 4 PULLS MADE THE JUNCTION BOX IS FIGURED BY MULTIPLYING THE CURGEST CONDUIT ENTRY (2"PVC) TIMES 6=12". A JUNCTION BOX 12"X12" IS THE MINIMUM REQUIRED. THE 6X6X4 IS TOO SMALL 4) UNDER STAND THE GAS BOND TO BE INSTALLED WHEN GAS LINE IS FINISHED
04/23/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0999*
04/20/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0999* IN ORDER TO BE ABLE TO DO THIS KIND OF WORK YOU MUST HAVE A C-11 ELECTRICAL LICENCED CONTRACTOR