Permit: T01EL00824

Parcel: 113092200


Addresses:

843 E WATER ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
05/03/2001 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
04/23/2001 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*1. SUPPORT CONDUIT AS PER CODE, 1/2" ABOVE PANEL. 2. USE CORRECT SPLICING METHODS FOR SPLIT BOLTS PANEL & JUNCTION BOX.
04/18/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0999* 1) LOOSE FITTING-LB
2) CLEAN SUFACE UNDER LUG 250-12 3) CAN NOT USE SHEET METAL SCREW 250-8 4) USE CORRECT SPLICING METHODS FOR SPIT BOLTS 5) NEED ALL STRANDS UNDER LUGS 6) TIGHTEN ALL FITTINGS ON TOP OF PANEL 7) SUPPORT ALL CONDUITS AS PER CODE 8) NEED 2 SUPPORTS BELOW ROOF LINE FOR RISER 9) PROTECT SE CABLE 10) CLEAN OUT BOTTOM OF PANEL