Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T01EL00821
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/18/2001 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* | |
| 04/16/2001 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0935* 1) POLES NOT SECURE IN GROUND A REFEE HAS BEEN ASSESED TO THIS JOB | |
| 04/13/2001 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999*LOCKED 11:30 A.M. | |
| 04/12/2001 | ELECTRIC - FINAL | Denied | SERVICE A: 1. BONDING DEVICE NEEDED BOTH SIDES OF NIPPLE 2. ID NEUTRAL CONDUCTOR CLOSER TO WEATHERHEAD 3. POLE NOT SECURE IN GROUND SERVICE B: 1. POLE NOT SECURE IN GROUND * HAVE LICENSED L-11 ELECTRICAL CONTRACTOR CALL THE OFFICE TO VERIFY WORK BEFOR NOXT INSPECTION. | |
| 04/10/2001 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999* 1) GROUND RODS TO BE IN CONTACT 8' WITH THE SOIL NOT BENT 2) ID NUMBER CONDUCTOR CLOSER TO WEATHER HEADS 3) NEED PERMANENT ADDRESS LABELS 4) USE APPROVED FITTINGS TO CONNEC TO OUTLET BOX 5) GROUND RODS TO BE 6' APART 6) VERIFY LICENCED L-11 ELEC. CONTACTOR 7) NEED BONDING DEVICE BOTH SIDES OF NIPPLE |