Addresses:

21 W ALCO ST

Inspection Status: Denied

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
04/11/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0999* 1) NEED GROUNDING ELECTRODE SYSTEM INSTALLED PER CODE. 2 RODS, WATER AND GAS BOND 2) WILL NEED A HANDLE TIE FOR 2 POLE BREAKER WILL REQUIRE HANDLE TIES
3) WILL NEED A LICENCED C-11 ELEC. CONTRACTOR
04/06/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0999* 1) ADDRESS HOUSE(USE 3" HIGH NUMBERS) 2) THE WATER LINE HAS BEEN REPLACED WITH PVC PIPING AND YOUR GROUNDING SYSTEM HAS BEEN COMPRIMISED. USE GROUND WIRE LEFT FROM OLD SYSTEM TO USE AS AN INTERIOR WATER BOND AND YOU WILL NEED TO INSTALL A NEW GROUNDING ELECTRODE SYSTEM IE:RODS ETC... 3) AT SERVICE YOU NEED FILLER PLATES AND A TIE BAR ON 2 POLE BREAKERS
4) THE WROUGHT IRON BARS ON THE 2 BEDROOM MUST BE REMOVED OR MADE SO AS TO RENDER QUICK RELEASE FOR AN EMERGENCY 5) OPEN WATER HEATER ROOM 6) INSTALL SMOKE DETECTOR 7) REPAIR/REPLACE FURNACE RECEPTICLE