Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T01EL00770
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/12/2001 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* | |
| 04/10/2001 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0245* 1) CHANGE NIPPLES NOT ALLOWED 2) INSTALL CLOSE NIPPLE WITH LOCKNUTS BOTH ENDS, INSTALL BOND BUSHINGS ON ALL CONCENTRIC KO'S PER 250-94 NEC 3) GROUND J BOX 370-4 NEC AND 250 NEC 4)USE MIN. 1/4" ANCHORS OR BOLTS TO SUPPORT RISER. |