Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/26/2001 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection 0000*OK TO CLEAR SERVICE | |
| 06/19/2001 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection 0245*PLASTIC IN BETWEEN GROUND CONNECTION AND INTERIOR WATER BOND-NEED PERMANENT ADDRESS TAG-NEED TO HAVE A LICENSED C-11 ELECTRICAL CONTRACTOR FOR JOB-CALL 791-5550 EXT.323 LEAVE NAME OF CONTRACTOR BEFORE NEXT INSPECTION. | |
| 05/23/2001 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection 0999*NO INSPECTION.REFEE NOT PAID | |
| 05/22/2001 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection 0245*A RE INSPECTION FEE IS DUE BEFORE THE NEXT IMSPECTION.1)NEED 2 RODS.2)I QUESTION THE INTERIOR WATER.THERE IS PLASTIC IN BETWEEN.WEED TO SEE A DIRECT CONNECTION TO INTERIOR.3)NEED PERMANENT ADDRESS TAG PER CITY. | |
| 05/03/2001 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection 0999* 1) EXPOSE GROUND ROD 2) INSTALL GAS AND WATER BOND |