Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 04/12/2001 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 04/05/2001 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0245* NOTES: 1) GROUND RODS MUST HAVE MIN. 6' SEPERATION BETWEEN PER ART 250 NEC 2) BREAKERS IN PANEL MUST BE OF SAME MANUFACTURER AS PANEL. CHECK 50 AMP BREAKER FOR STOVE (NO LABEL) |