Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 04/06/2001 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 04/04/2001 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0235* THE 99 NEC ART 250 104 86 ETC NOW REQUIRES THE GAS PIPING BE BONDED TO THE PANEL. PLEASE CORRECT AND RECALL SEE UNDER "OTHER PIPING ON PREMISES" |