Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T01EL00756

Parcel: 115043790

Inspection Status: Denied

Inspection History: ELECTRIC - FINAL

Permit Number - T01EL00756

Inspection Description - ELECTRIC - FINAL

Inspection Status - Denied

Date Description Inspector Results Comments
04/03/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0999* 1) DERATE FOR CONDUCTORS 310-15 2) CONDUCTOR SIZED TOO SMALL FOR BREAKER #10 ON 50AMP BREAKER 3) LABEL BREAKERS 4) FILL ALL UNUSED OPENINGS 5) BOND WATER 6) BOND JUNCTION BOX 7) PERMIT T98BU1305 OR CURRENT PERMIT FOR THIS PROJECT NEEDS TO BE COMPLETED BEFORE POWER CAN BE ENERGIZED