Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
Permit Number - T01EL00756
Inspection Description - ELECTRIC - FINAL
Inspection Status - Denied
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/03/2001 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999* 1) DERATE FOR CONDUCTORS 310-15 2) CONDUCTOR SIZED TOO SMALL FOR BREAKER #10 ON 50AMP BREAKER 3) LABEL BREAKERS 4) FILL ALL UNUSED OPENINGS 5) BOND WATER 6) BOND JUNCTION BOX 7) PERMIT T98BU1305 OR CURRENT PERMIT FOR THIS PROJECT NEEDS TO BE COMPLETED BEFORE POWER CAN BE ENERGIZED |