Inspection History: ELECTRIC - FINAL
Permit Number - T01EL00741
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/24/2001 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* | |
04/17/2001 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999*FINISH # 3-5 OF PREVIOUS INSPECTION 1. WORKING CLEARANCES FOR OVERHEAD CONDUCTORS. | |
04/11/2001 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999* 1) CLEAN SURFACE UNDER LUG IN METER SOCKET 250-12 2) LABEL BREAKERS 3) NEED ANTI-OXIDE COMPOUND ON ALUMINUM CONDUCTORS 4) ANCHORS COMING OUT OF WALL 5) LOOSE LOCKNUT SERVICE NIPPLES 6) LOOSE LUG BONDING BUSHING |
|
04/06/2001 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0945* COULD NOT LOCATE SERVICE- PLEASE LEAVE MESSAGE FOR NEXT INSP |