Inspection History Details
Inspection Status: Not ready for Inspection
Inspection History: ELECTRIC - FINAL
Permit Number - T01EL00722
Inspection Description - ELECTRIC - FINAL
Inspection Status - Not ready for Inspection
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/16/2001 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection 0000* 1) PLEASE HAVE COMPANY LETTER ON HAND INDICATING THAT THE ELECTRICAL HAS BEEN INSPECTED AND ALL UNUSED WIRING HAS BEEN REMOVED AND ALL REMAINING EXSISTING IS RENDERED SAFE UNDER EXSISTING CONDITION 2) MARK ALL 6 SERVICE DISCONNECTS WITH MIN OF 1" PERMANENT TYPE TAGGING ALL OTHER AREAS- SUB PANEL, LIGHT AND MISCELLANEOUS APPROVED | |
03/29/2001 | ELECTRIC - FINAL | Denied | 1) THER ARE TOO MANY PROBLEMS WITH THIS STORE IN ORDER TO RELEASE. IT APPEARS WHEN LAST OCCUPANTS LEFT NUMEROUS ELECTRICAL ITEMS WRE TAKEN AND THERE IS QUITE A BIT OF DAMAGED ELECTRICAL WIRING THRU OUT BEGINING AT SERVICE TO THRU OUT BLDG, BROKEN CONDUITS OPEN WIRING, LOOSE TERMINATIONS AT PANELS 2) YOU WILL BE REQUIRED TO OBTAIN THE SERVICES OF AN L-11 ELECTRICAL CONTRACTOR TO CLEAN UP DAMAGED WIRING, TO VERIFY CONNECTIONS ON ALL PANELS, INCLUDING ALL SERVICE EQUIPMENT, HE WILL BE REQUIRED TO OBTAIN A GENERAL REPAIR PERMIT, DO ALOL OF THE ABOVE AND CHECK ALL ROOF EQUIPMENT TO VERIFY TO COT THAT THIS BLDG IS ELEC. SAFE 3) WHEN ALL ITEMS ABOVE CORRECTED CALL FOR REINSP. AND ARRANGE FOR INSP. TO MEET CONTRACTOR TO REVIEW BLDG 4) CLEARANCE SUBJECT TO FIRE DEPT. CLEARANCE PER CARL SCHULTZ FIRE INSP. |