Inspection Status: Denied
Inspection History: ELECTRIC - RECONNECT
| Date |
Description |
Inspector |
Results |
Comments |
| 03/30/2001 |
ELECTRIC - RECONNECT |
|
Denied |
IVRS - Inspection 0245* 1) GROUND CONDUCTORS SHOW EVIDENCE OF OVER HEATING BY DISCOLORATION OF COPPER WIRE FROM SHINY COPPER TO DARK AT POINTS OF TERMINATION (PANEL E) 2) NEED LICENCED ELEC. CONTRACTOR TO CHECK OUT SYSTEM AND VERIFY THE INTEGRITY OF WIRING AND NOTIFY CITY DSC BY FAX OR LETTER PRIOR TO RELEASE OF POWER |
| 03/29/2001 |
ELECTRIC - RECONNECT |
|
Denied |
IVRS - Inspection 0920* IDENTIFY PANEL "E" AND LOCATION |