Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T01EL00715

Parcel: 126010520

Inspection Status: Denied

Inspection History: ELECTRIC - RECONNECT

Date Description Inspector Results Comments
03/30/2001 ELECTRIC - RECONNECT Denied IVRS - Inspection 0245* 1) GROUND CONDUCTORS SHOW EVIDENCE OF OVER HEATING BY DISCOLORATION OF COPPER WIRE FROM SHINY COPPER TO DARK AT POINTS OF TERMINATION (PANEL E) 2) NEED LICENCED ELEC. CONTRACTOR TO CHECK OUT SYSTEM AND VERIFY THE INTEGRITY OF WIRING AND NOTIFY CITY DSC BY FAX OR LETTER PRIOR TO RELEASE OF POWER
03/29/2001 ELECTRIC - RECONNECT Denied IVRS - Inspection 0920* IDENTIFY PANEL "E" AND LOCATION