Inspection History Details
Inspection Status: Approved
Inspection History: SIGN ELECTRIC
Permit Number - T01EL00703
Inspection Description - SIGN ELECTRIC
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/11/2001 | SIGN ELECTRIC | Approved | IVRS - Inspection 0000* | |
07/06/2001 | SIGN ELECTRIC | Denied | IVRS - Inspection 0999*CORRECTIONS NOT MADE PER PREVIOUS ORDER 1.) YOU MAY NOT LOOP GTO CABLE INSIDE PULL BOXES 2.) THE FLEX CONDUIT ON WALL IS WHAT NEED TO BE SECURED. ANY LENGHT OVER 3 1/2 REQUIRES SUPPORT PER NEC 350-18 3.) BOLT TRANSFORMERS DOWN 4.) SMOKE DAMPER WALL (DRYWALL) WILL NEED TO BE REPLACED WHERE IT WAS KNOCKED OUT. | |
06/21/2001 | SIGN ELECTRIC | Denied | IVRS - Inspection 0999*SIGN ELECTRIC DENIED 1.) EXCESS G TO CABLE INSIDE PULL BOXES 2.) FLEX CONDUIT TO BE SECURED WITHIN 12" OF EACH TERMINATION AND EVERY 3 1/2 OF LENGTH (EXCEPT FOR LENGHTS LESS THAN 3 1/2" 3.) BOLT TRANSFORMERS DOWN SO THEY CANT BE KNOCKED OVER 4.) TIGHTEN ALL FLEX FITTINGS | |
04/09/2001 | SIGN ELECTRIC | Denied | IVRS - Inspection 0999* NO ACCESS TO INSPECT SUB PANEL. PLEASE CALL ME WHEN SOMEONE WILL BE IN STORE. |