Inspection History: SIGN ELECTRIC
Permit Number - T01EL00702
Inspection Description - SIGN ELECTRIC
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/09/2001 | SIGN ELECTRIC | Approved | IVRS - Inspection 0000* | |
04/25/2001 | SIGN ELECTRIC | Denied | IVRS - Inspection 0999* 1) APPLY CAULK TO SEAL OPENING DRILLED THROUGH WALL FOR PRIMARY CONDUIT 2) BOND JUNCTION BOX IN SIGN AND IN PORCH TO GROUND OR PROVIDE PROOF THAT CONDUIT IS BONDED ALL THE WAY BACK TO SERVICE PANEL. 3) FITTINGS ON CONDUIT SHOULD BE WRENCH TIGHT 4) ID SIGN CIRCUIT AT SUB PANEL |