Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/10/2001 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* | |
| 05/08/2001 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0245* 1) OK FOR CABLE DROP, BUT NO METER UNTIL GROUNDING ELECTRODE SYSTEM IS INSTALLED PROPERLY 2) IF THE INTENTION IS TO BURY GROUND RODS IN TRENCH DO NOT DO SO UNTIL TRENCH IS AT LEAST 2 1/2' DEEP PER NEC. AND HAS BEEN INSPECTED AND APPROVED. 3) STILL NOT IN COMPLIANCE WITH ITEMS 1,2,4 OF LAST WRITE UP |
|
| 05/01/2001 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0245* NO PROGRESS SINCE LAST INSPECTION 4-26-01. PLEASE PAY RE INSP. FEE | |
| 04/26/2001 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0245* 1) INSTALL BUSHING IN KO BACK OF PANEL TO PROTECT #8 ROMEX FROM ABRASION 300-16 NEC 2) NEW CKT 30 AMP HAS NO GROUND CONDUCTOR, IT APPEARS WIRE INSULATION OUTER JACKET WAS STRIPPED BEFORE ENTERING PANEL? 3) SUPPORT 1/2" EMT WITHIN 3' OF PANEL 348-13 NEC 4) WATER PIPE MUST BE BONDED TO SERVICE 5) GAS MUST BE BONDED TO SERVICE 6) GROUND ROD TO BE DRIVEN INTO EARTH UNLESS SOLID ROCK IS ENCOUNTERED 7) EVEN IF HARD ROCK IS ENCOUNTERED TRENCH MUST BE 2 1/2' DEEP 30" |