Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/11/2001 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection 0000* | |
| 04/05/2001 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection 0920* LOCKED NO ACCESS BACK GATE LOCKED AND DOG |
|
| 04/03/2001 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection 0999* 1) WORKING CLEARANCE IN FRONT OF PANEL GATE 2) LABEL BREAKERS 3) NEED BONDING DEVICE ON CONDUIT CARRING GROUNDING CONDUCTOR BOTH ENDS 4) LOOSE FITTINGS 5) GROUND ROD TO BE A FULL 8' IN LENGTH 6) ID NEUTRAL CONDUCTOR CLOSER TO WEATHER HARD |