Permit: T01EL00696

Parcel: 115043010


Addresses:

1207 N 6TH AV

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
04/11/2001 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection 0000*
04/05/2001 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection 0920* LOCKED NO ACCESS
BACK GATE LOCKED AND DOG
04/03/2001 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection 0999* 1) WORKING CLEARANCE IN FRONT OF PANEL GATE 2) LABEL BREAKERS 3) NEED BONDING DEVICE ON CONDUIT CARRING GROUNDING CONDUCTOR BOTH ENDS 4) LOOSE FITTINGS 5) GROUND ROD TO BE A FULL 8' IN LENGTH 6) ID NEUTRAL CONDUCTOR CLOSER TO WEATHER HARD