Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T01EL00673

Parcel: 134250670


Addresses:

1026 S LEHIGH DR

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
04/09/2001 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection 0000*
03/28/2001 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection 0220* THE COLD WATER AND GAS PIPING MUST BE BONDED TO THE PANEL NEUTRAL. ALL CLAMPS MUST BE VISIBLE. SEE DRAWING ON INSP. SHEET.(NO SPLICES ALLOWED)