Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T01EL00631

Parcel: 137053470


Addresses:

758 W MONTANA ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
03/29/2001 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
03/19/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0245* 1) #8 ROMEX NOT APPROVED FOR 50 AMPS 2) 1/2" CHASE NIPPLE NOT APPROVED, MUST BE CLOSE NIPPLE WITH LOCKNUTS BOTH ENDS