Permit: T01EL00627

Parcel: 124052040


Addresses:

1012 E 6TH ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
04/09/2001 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
04/03/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0999* 1) LOOSE SEAL TITE FITTINGS
2) MOVE SEAL TITE SO AS NOT TO CUT INTO WITH HOUSING 3) LOOSE CONDUIT FITTING 4) STRAP CONDUIT PER CODE 5) SEAL CONDUIT ENTERING WALK IN BOX 6) EXPOSED CONDUCTORS WALK IN BOX 7) CAN NOT LOCATE LISTING LABEL ON STEAM TABLE
03/30/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0999* 1) NEED WEATHER PROOF FITTINGS OUT DOORS 2) BOND JUNCTION BOX
3) FILL ALL UNUSED OPENINGS IN PANEL 4) LABEL BREAKERS OUTSIDE PANEL 5) USE APPROVED FITTINGS TO LB-CHASE NIPPLE NOT APPROVED
6) CANNOT LOCATE GROUND ROD'S 7) LABEL DISCONNECTS 8) LABEL PANELS 9) NEED WEATHER PROOF COVER ON OUTLET UNDER SCRUB SINK 10) NEED LISTING AND LABELING FOR KITCHEN EQUIPMENT 11) BROKEN MC OR BX CABLE AT BATH LIGHT 12) FINISH ELECTRIC WORK TO CODE