Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/19/2001 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection 0000* SUBJECT TO TEP REGARDING SEC SR-405-10 (L) | |
| 03/14/2001 | ELECTRIC - SERVICE UPGRADE | Denied | 1) NEED PERMANENT ADDRESS LABELS 2) LABEL BREAKERS 3) LOOSE SEAL TITE FITTINGS. 4) EXPOSED CONDUCTOR ABOVE PANEL AND ON ROOF 5) NEED WATER AND GAS BOND 6) ILLEGALE SPLICES FOR BOX ABOVE WATER HEATER AND STORAGE ROOM 7) EXPOSED ROMEX BELOW 8' 8) MISSING FACE PLATES 9) NEED GUY BACK BRACE |