Inspection History Details
Inspection Status: Partial Approval
Inspection History: ELECTRIC - FINAL
Permit Number - T01EL00555
Inspection Description - ELECTRIC - FINAL
Inspection Status - Partial Approval
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/18/2001 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000* | |
04/10/2001 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection 0000* 1) 200A PANEL AT OFFICE BLDG HAS 100A FEED TO NORTH SECTION 8 TRAILERS. THIS IS TOO MUCH FOR THIS PANEL, ALREADY HAS 19 30 AMP CIRCUITS FOR TRAILERS PLUS A 60 AMP FEED FOR OFFICE. 100 AMP FEED HAS TO BE RELOCATED 2) METERS AND DISCONNECTES FOR INDIVIDUAL TRAILERS WILL NEED TO BE SUPPORTED RIGIDLY. FENCE POST SUPPORTS IN ADEQUATE 3) BURIAL DEPTH 12" ON AVERAGE. THIS WILL REQUIRE 2" OF CONCRETE ABOVE UF FEEDERS 4) ID CIRCUIT BREAKERS AS TO THEIR TRAILERS 5) 2 LOOSE NON TERMINATED #10'S UF AT END OF EAST SIDE LOOP | |
04/09/2001 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999* |